DocumentCode
3262412
Title
Real-time load compensation by using a cascaded multilevel inverter-based STATCOM
Author
Chang, Wei-Neng ; Liao, Ching-Huan
Author_Institution
Dept. of Electr. Eng., Chang Gung Univ., Taoyuan, Taiwan
fYear
2011
fDate
5-8 Dec. 2011
Firstpage
840
Lastpage
846
Abstract
A delta-connected static synchronous compensator (STATCOM) is proposed for real-time load compensation of unbalanced load. The structure of the STATCOM is a multilevel cascaded full H-bridge inverter which is suitable for high-voltage, high-power applications. First, use of the symmetrical components method derives the control algorithm of the STATCOM. The STATCOM is then built in the Matlab/Simulink environment. Finally, simulation results indicate that the proposed delta-connected STATCOM is effective for real-time load compensation of unbalanced loads.
Keywords
invertors; static VAr compensators; Matlab-Simulink environment; cascaded multilevel inverter-based STATCOM; delta-connected static synchronous compensator; multilevel cascaded full H-bridge inverter; real-time load compensation; symmetrical components; Automatic voltage control; Inverters; Load management; Reactive power; Real time systems; Simulation; Switches; Delta connected STATCOM; Full h-bridge; Load compensation; Symmetrical components method;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics and Drive Systems (PEDS), 2011 IEEE Ninth International Conference on
Conference_Location
Singapore
ISSN
2164-5256
Print_ISBN
978-1-61284-999-7
Electronic_ISBN
2164-5256
Type
conf
DOI
10.1109/PEDS.2011.6147352
Filename
6147352
Link To Document