DocumentCode
3268132
Title
Computer controlled load-shedding for a co-generation facility
Author
Caballer, Miguel A. ; Kassebaum, John H. ; Stratford, Ray P. ; Delaney, Lawrence
fYear
1992
fDate
28-30 Sep 1992
Firstpage
247
Lastpage
254
Abstract
The installation of a load shedding and load restoration system used in conjunction with a cogeneration installation is described. When the utility source fails, the generators will be shut down by their under frequency relays unless the overload is shed. The load shedding system continuously monitors the sheddable loads as well as the generator and utility source capabilities. When any of these sources fail, loads are shed on a predetermined but changeable priority basis before the under frequency relays operate to shut down the generators. This same project involved the installation of synchronizing and paralleling equipment for two smaller high-speed standby diesel generators. The various aspects of the design and installation, including design criteria, software development, and hardware selection are described
Keywords
cogeneration; diesel-electric generators; emergency power supply; load shedding; power station computer control; power station load; power system computer control; power system restoration; standby generators; synchronisation; thermal power stations; cogeneration; design; emergency power supply; generator; hardware; installation; load restoration; load shedding; power systems; project; software; standby diesel generators; synchronisation; under frequency relays; Cogeneration; Pharmaceutical technology; Power generation; Power system relaying; Power system restoration; Programming; Relays; Senior members; Software design; Standby generators;
fLanguage
English
Publisher
ieee
Conference_Titel
Petroleum and Chemical Industry Conference, 1992, Record of Conference Papers., Industry Applications Society 39th Annual
Conference_Location
San Antonio, TX
Print_ISBN
0-7803-0750-X
Type
conf
DOI
10.1109/PCICON.1992.229304
Filename
229304
Link To Document