• DocumentCode
    3268603
  • Title

    Changes in hazardous locations requirements in the 1993 National Electrical Code

  • Author

    Ballard, A.W. ; Sengupta, S.

  • Author_Institution
    Crouse-Hinds, Syracuse, NY, USA
  • fYear
    1992
  • fDate
    28-30 Sep 1992
  • Firstpage
    43
  • Lastpage
    47
  • Abstract
    The National Electrical Code revision process is discussed, as are many of the proposals incorporated into the 1993 NEC. Nonincendive circuits are contrasted with nonincendive components. Resistivity is no longer used in classifying dusts, and coal is now considered nonconductive. Class II surface temperatures may now be based on the specific dust, not only the group involved. Proposals for Division 0 were rejected and this issue, including `increased safety´ is examined in detail. Type AC cable is excluded as a wiring method in hazardous locations. In Class I, a new method for sealing multiconductor cable in conduit is approved, as are additional types of cable tray in Cable II, Division 2
  • Keywords
    electric conduits; power cables; safety; standards; 1993 National Electrical Code; Class II surface temperatures; cable tray; coal; conduit; hazardous locations requirements; multiconductor cable sealing; nonincendive circuits; nonincendive components; safety; Circuit testing; Conductivity; Documentation; Grounding; IEEE members; National electric code; Proposals; Safety; Temperature; Wiring;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Conference, 1992, Record of Conference Papers., Industry Applications Society 39th Annual
  • Conference_Location
    San Antonio, TX
  • Print_ISBN
    0-7803-0750-X
  • Type

    conf

  • DOI
    10.1109/PCICON.1992.229328
  • Filename