• DocumentCode
    3276279
  • Title

    Simulated Electromagnetic Field Profile Inside and Outside XLPE Power Cable due to Partial Discharge

  • Author

    Ghani, A.B.A. ; Shafi, H. ; Chakrabarty, C.K.

  • Author_Institution
    College of Engineering, University Tenaga Nasional, Kajang, 43000 Malaysia. E-mail: basriag@yahoo.co.uk
  • fYear
    2007
  • fDate
    8-13 July 2007
  • Firstpage
    71
  • Lastpage
    74
  • Abstract
    The electromagnetic field profile due to partial discharge is simulated. The x, y and z components of the electric and magnetic fields are calculated at the azimuthal plane of the single core xlpe cable, at the near field and far field regions inside and outside the cable. The results from the simulation give indication that the propagation mode of partial discharge signal at near field is hybrid transverse electric & transverse magnetic mode. The propagation mode at the far field region inside the power cable is transverse electric magnetic; and the propagation mode of the partial discharge outside the cable is quasi transverse electric magnetic.
  • Keywords
    Dipole antennas; Electromagnetic fields; Electromagnetic radiation; Finite difference methods; Partial discharges; Power cables; Pulse shaping methods; Shape; Space vector pulse width modulation; Time domain analysis;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
  • Conference_Location
    Winchester, UK
  • Print_ISBN
    1-4244-0750-8
  • Electronic_ISBN
    1-4244-0751-6
  • Type

    conf

  • DOI
    10.1109/ICSD.2007.4290755
  • Filename
    4290755