Degradation of Epoxy in Stator Insulation in Service 23 Years for A Large Generator
Author :
Hao, Y.P. ; Wang, X.L. ; Xie, H.K.
Author_Institution :
The Electric Power College, South China University of Technology, Guangzhou 510640, China. E-mail: yphao@scut.edu.cn
fYear :
2007
fDate :
8-13 July 2007
Firstpage :
314
Lastpage :
317
Abstract :
The degradation behavior of epoxy in stator insulation under operating stresses was invested by thermogravimetry and infrared spectrometry. The insulation specimens were cut from a standby and an aged stator bar in operation for 23 years in a 300MW/18kV generator. It is found there are two aging processes of epoxy in the aged insulation. One is weight loss measured by thermogravimetry increases, while the absorption intensities due to ¿OH, C=O groups increase, and those due to ¿CH3, ¿CH2 groups obtained by infrared spectrometry decrease, demonstrating the oxidation occurred on branched chains of epoxy. The other is more two decompose processes appear in the TG curves, in addition to decompose of epoxy, while the absorption intensity due to C-C group decrease, revealing the rupture of fundamental chains of epoxy.
Keywords :
Aging; Degradation; Electromagnetic wave absorption; Infrared spectra; Insulation; Loss measurement; Spectroscopy; Standby generators; Stators; Thermal stresses;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
Conference_Location :
Winchester, UK
Print_ISBN :
1-4244-0750-8
Electronic_ISBN :
1-4244-0751-6
Type :
conf
DOI :
10.1109/ICSD.2007.4290815
Filename :
4290815
Link To Document :
بازگشت