Title : 
New Out of Step Blocking Algorithm for Detecting Fast Power Swing Frequencies
         
        
            Author : 
Holbach, Juergen
         
        
        
        
        
        
            Abstract : 
This paper will describe a new algorithm for detecting the out of step and power swing condition. This algorithm, which is based on continuous impedance monitoring, doesn´t require a blinder or concentric characteristics. Therefore no settings are needed. The algorithm continuously monitors the speed and the shape of the impedance trajectory and will immediately see the start of a power swing cycle or an out of step condition. This detection also enables the algorithm to detect fast swing cycles with swing frequencies up to 7 Hz. Solution to three pole fault detection is by a ripple on space vector
         
        
            Keywords : 
fault diagnosis; power system faults; continuous impedance monitoring; out of step blocking algorithm; power swing frequency; space vector ripple; three pole fault detection; Change detection algorithms; Electrical fault detection; Fault detection; Frequency; Impedance; Logic; Power system faults; Protection; Protective relaying; Voltage;
         
        
        
        
            Conference_Titel : 
Power Systems Conference: Advanced Metering, Protection, Control, Communication, and Distributed Resources, 2006. PS '06
         
        
            Conference_Location : 
Clemson, SC
         
        
            Print_ISBN : 
0-615-13280-4
         
        
        
            DOI : 
10.1109/PSAMP.2006.285388