DocumentCode :
3279247
Title :
On-site Diagnostic Tests on Polymer Insulated Cables Using Depolarization Current Measurements
Author :
Dakka, M. Abou ; Bulinski, A. ; Bamji, S.
Author_Institution :
National Research Council of Canada, Ottawa, Ontario, Canada, K1A 0R6. E-mail: mahmoud. abou-dakka@nrc-cnrc.gc.ca
fYear :
2007
fDate :
8-13 July 2007
Firstpage :
725
Lastpage :
728
Abstract :
Amodified technique of depolarization current measurements encompassing monitoring of high speed depolarization processes was used to perform diagnostic tests on polymeric cable insulation operating under diverse environmental conditions and voltage levels. The high frequency characteristics were compared with those of the slower depolarization processes commonly obtain during on-site tests. Both the high and low frequency measurements showed a consistent correlation with the operating conditions of the cable insulation. It was observed that the low frequency characteristics were dependent on the duration of the dc poling time but only if the insulation was deteriorated, especially with water trees. Unaged and relatively new insulation did not show such behavior. The majority of the field tests were performed with a relatively low dc voltage of only 1 kV or less and under very adverse environmental conditions, with temperatures as low as ¿30°C.
Keywords :
Cable insulation; Cables; Condition monitoring; Current measurement; Frequency; Insulation testing; Performance evaluation; Plastic insulation; Polymers; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Solid Dielectrics, 2007. ICSD '07. IEEE International Conference on
Conference_Location :
Winchester, UK
Print_ISBN :
1-4244-0750-8
Electronic_ISBN :
1-4244-0751-6
Type :
conf
DOI :
10.1109/ICSD.2007.4290916
Filename :
4290916
Link To Document :