DocumentCode :
3279359
Title :
Parallel redundant operation of UPS with robust current minor loop
Author :
Ito, Youichi ; Iyama, Osamu
Author_Institution :
Sanken Electr. Co. Ltd., Saitama, Japan
Volume :
1
fYear :
1997
fDate :
3-6 Aug 1997
Firstpage :
489
Abstract :
This paper describes a control method of UPS inverters connected in parallel. The UPS output voltage is controlled by an algorithm with an inverter current. A minor loop using two types of observers. Only the following two points are added to the algorithm for realizing parallel operations: (1) feedback of a common load current instead of the UPS output current; and (2) adjusting the phase of the output voltage to make the reactive component of the circulating currents zero. The proposed method has the following features, compared with conventional methods; (1) it does not need an additional output voltage control for parallel operation; (2) the impedances among UPSs are resistive so that the circulating currents caused by phase difference among UPSs have only reactive components; and (3) increase of software for parallel operation control is minimal
Keywords :
electric current control; electric impedance; feedback; invertors; observers; redundancy; robust control; uninterruptible power supplies; voltage control; UPS; UPS inverters; UPS output voltage control; circulating currents; common load current feedback; observers; output voltage phase adjustment; parallel connected inverters; parallel redundant operation; phase difference; reactive component; resistive impedances; robust current minor loop; Impedance; Indium tin oxide; Inverters; Output feedback; Power supplies; Power system reliability; Process control; Robustness; Uninterruptible power systems; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Conversion Conference - Nagaoka 1997., Proceedings of the
Conference_Location :
Nagaoka
Print_ISBN :
0-7803-3823-5
Type :
conf
DOI :
10.1109/PCCON.1997.645660
Filename :
645660
Link To Document :
بازگشت