• DocumentCode
    33068
  • Title

    Optimal Operation of Long Inhomogeneous AC Cable Lines: The Malta–Sicily Interconnector

  • Author

    Lauria, S. ; Palone, F.

  • Author_Institution
    Dept. of Astronaut., Electr. & Energy Eng., “Sapienza” Univ. of Rome, Rome, Italy
  • Volume
    29
  • Issue
    3
  • fYear
    2014
  • fDate
    Jun-14
  • Firstpage
    1036
  • Lastpage
    1044
  • Abstract
    This paper presents a new approach to optimal exploitation and reactive power control of long inhomogeneous high-voltage ac cable lines, such as submarine interconnectors including significant land cable stretches. Voltage and reactive power profiles are discussed, highlighting the requirements for full exploitation of power transmission capacity, and giving formulae for optimal voltage control. Capability curves for the lossy inhomogeneous cable line are discussed; this paper also proposes a simple algorithm for controlling the reactive power flow at one end of the line independently from active power, using variable shunt reactors and tap-changing transformers. The application of the presented treatment to a real inhomogeneous line, that is, the 118-km-long 245-kV-50-Hz Malta-Sicily interconnector currently under construction, yields maximum power and optimal voltage drop values in close agreement with detailed simulation results. Power-flow simulations also confirm the effectiveness of the proposed reactive power control algorithm. Finally, total transmission losses associated with the proposed optimal voltage control are evaluated and shown to be competitive with those of state-of-the-art HVDC-VSC systems.
  • Keywords
    HVDC power transmission; electric potential; high-voltage techniques; load flow; power cables; power convertors; power system interconnection; power transformers; power transmission control; reactive power control; voltage control; HVDC-VSC systems; Malta-Sicily interconnector; capability curves; distance 118 km; frequency 50 Hz; inhomogeneous high-voltage AC cable lines; lossy inhomogeneous cable line; optimal exploitation; optimal voltage control; optimal voltage drop; power drop; power flow simulation; power transmission capacity exploitation; reactive power control; tap-changing transformers; transmission losses; variable shunt reactors; voltage 245 kV; Inductors; Nonhomogeneous media; Power cables; Propagation losses; Reactive power; Shunts (electrical); Capability curves; HV ac cables; reactive power; shunt compensation; submarine power transmission;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2013.2293054
  • Filename