Power system contingency analysis-an improved technique based on Tellegen theorem
Author
Golob, R. ; Gubina, F.
Author_Institution
Fac. of Electr. & Comput. Eng., Ljubljana Univ., Slovenia
Volume
1
fYear
1996
fDate
12-15 May 1996
Firstpage
661
Abstract
In the paper, an improved algorithm based on Tellegen theorem is proposed for power system contingency analysis. The main feature of the improved algorithm is calculation of post-perturbation nodal variables utilizing a fast non-iterative procedure. For that purpose, new modeling of voltage controlled (PV) nodes is introduced to account for PV bus response to a given perturbation. The improved adjoint network method was tested on several test systems and its results were compared to those obtained with other power flow based techniques, i.e. fast decoupled power flow and 1P1Q method. The tests show that the improved adjoint network method performs faster for large power systems while keeping the accuracy of post perturbation solution on the same level as widely accepted 1P1Q method
Keywords
perturbation techniques; power system analysis computing; power system planning; PV bus response; Tellegen theorem; adjoint network; algorithm; contingency analysis; model; noniterative method; perturbation analysis; post-perturbation nodal variables; power flow; power system; voltage controlled nodes; Computer networks; Equations; Iterative algorithms; Load flow; Power system analysis computing; Power system modeling; Power system security; Power systems; System testing; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Circuits and Systems, 1996. ISCAS '96., Connecting the World., 1996 IEEE International Symposium on
Conference_Location
Atlanta, GA
Print_ISBN
0-7803-3073-0
Type
conf
DOI
10.1109/ISCAS.1996.540034
Filename
540034
Link To Document