On resistive grounding of neutral point of APP network
Author
Ivanov, A.V.
Author_Institution
Novosibirsk State Tech. Univ., Russia
fYear
2003
fDate
7-11 April 2003
Firstpage
27
Lastpage
29
Abstract
In this paper, the results of atomic power plant (APP) house system operation modes analysis, the selection of the optimal value of the neutral point grounding resistance of the network, the selection of the place for the special neutrals assignment transformer installation, to which the resistors are connected as well as the capabilities of parallel connection of ground-fault neutralizers and resistors are considered. By installing high ohmic resistors of 500 ohms into the neutrals assignment transformers, the currents of the single-phase ground amount to 10 to 20 A, lower than those with the installation of low ohmic resistors of 100 ohms. Resistors of 500 ohms are not disconnected in processes tracking the single-phase ground and the single-phase arc ground.
Keywords
earthing; nuclear power stations; resistors; atomic power plant; ground-fault neutralizer; house system; nuclear reactor; point grounding resistance; resistive grounding; special neutrals assignment transformer installation; Emergency power supplies; Feeds; Grounding; Power generation; Power transformer insulation; Renewable energy resources; Resistors; Surges; Thermal resistance; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Modern Techniques and Technologies, 2003. MTT 2003. Proceedings of the 9th International Scientific and Practical Conference of Students, Post-graduates and Young Scientists
Print_ISBN
0-7803-7669-2
Type
conf
DOI
10.1109/SPCMTT.2003.1438112
Filename
1438112
Link To Document