DocumentCode
331531
Title
Spectral analysis of leakage current on contaminated insulators by auto regressive method
Author
Sato, M. ; Nakajima, A. ; Komukai, T. ; Oyamada, T.
Author_Institution
Akita Univ., Japan
Volume
1
fYear
1998
fDate
25-28 Oct 1998
Firstpage
64
Abstract
This paper presents the results of spectral analysis of leakage current waveforms on contaminated insulators under fog conditions. This is a basic study on the development of a monitoring system for substation insulators under contamination conditions. The spectral analysis of the leakage current waveforms was conducted by the Auto Regressive (AR) method with high resolution and without limitation in number of sampling data. The comparative study was done on the initial values of ESDD and NSDD, the salt-fog density and the applied voltage using the power spectra obtained. The results indicate that the spectral analysis by the AR method is available for the monitoring of contamination conditions of outdoor insulators
Keywords
insulator contamination; insulator testing; leakage currents; spectral analysis; substation insulation; ESDD; NSDD; auto regressive method; contamination monitoring; fog; leakage current; outdoor insulator; power spectra; salt-fog density; spectral analysis; substation; Condition monitoring; Insulation; Leakage current; Pollution measurement; Sampling methods; Spectral analysis; Substations; Surface contamination; Surface discharges; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on
Conference_Location
Atlanta, GA
Print_ISBN
0-7803-5035-9
Type
conf
DOI
10.1109/CEIDP.1998.733851
Filename
733851