DocumentCode :
331533
Title :
Insulation deterioration of a 66 kV line-post insulator covered with salt-ice
Author :
Sugawara, N. ; Tanishima, K. ; Saito, A. ; Yamanouchi, K.
Author_Institution :
Kitami Inst. of Technol., Hokkaido, Japan
Volume :
1
fYear :
1998
fDate :
25-28 Oct 1998
Firstpage :
92
Abstract :
In order to study the insulation deterioration and flashover performance of transmission-line insulators in seasalt and freezing weather, measurements of DC leakage resistance and flashover tests were carried out in a cold room. These experimental results of comparison between DC leakage resistance and flashover events show that R1 higher or lower than 1×104 Ω has a higher probability of flashover occurrence
Keywords :
environmental degradation; flashover; ice; insulator contamination; power transmission lines; 66 kV; DC leakage resistance; flashover; line-post insulator; salt-ice; surface contamination; transmission line insulation; Conductivity; Electrical resistance measurement; Flashover; Ice; Insulation; Ocean temperature; Pollution measurement; Sea measurements; Snow; Wind;