Title :
Insulation deterioration of a 66 kV line-post insulator covered with salt-ice
Author :
Sugawara, N. ; Tanishima, K. ; Saito, A. ; Yamanouchi, K.
Author_Institution :
Kitami Inst. of Technol., Hokkaido, Japan
Abstract :
In order to study the insulation deterioration and flashover performance of transmission-line insulators in seasalt and freezing weather, measurements of DC leakage resistance and flashover tests were carried out in a cold room. These experimental results of comparison between DC leakage resistance and flashover events show that R1 higher or lower than 1×104 Ω has a higher probability of flashover occurrence
Keywords :
environmental degradation; flashover; ice; insulator contamination; power transmission lines; 66 kV; DC leakage resistance; flashover; line-post insulator; salt-ice; surface contamination; transmission line insulation; Conductivity; Electrical resistance measurement; Flashover; Ice; Insulation; Ocean temperature; Pollution measurement; Sea measurements; Snow; Wind;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1998. Annual Report. Conference on
Conference_Location :
Atlanta, GA
Print_ISBN :
0-7803-5035-9
DOI :
10.1109/CEIDP.1998.733862