Abstract
Valve-regulated lead acid (VRLA) batteries have been deployed widely as backup energy reserve for telecommunication applications, particularly in outdoor installations. Two issues have been raised for the VRLA batteries in these uncontrolled environments, namely, thermal runaway and excessive hydrogen gassing. In this work, a battery aging process is proposed to show that a large number of shorted batteries (zero float voltage) is unlikely during thermal runaway of a string of batteries. Failure analysis of field batteries and laboratory polarization results are presented. In thermal aging, the internal resistance was found to increase and will impact the amount of float current that can be passed through the string. The float current can only reach a limiting value and drop with increasing internal resistance
Keywords
ageing; electric resistance measurement; failure analysis; hydrogen; lead; polarisation; secondary cells; telecommunication power supplies; thermal analysis; Pb; Pb-acid valve regulated batteries; battery aging process; excessive hydrogen gassing; failure analysis; float current; internal resistance increase; laboratory polarization results; outdoor installations; thermal aging; thermal runaway; uncontrolled environments; valve-regulated lead acid batteries; zero float voltage; Aging; Batteries; Circuits; Corrosion; Electrical resistance measurement; Failure analysis; Hydrogen; Temperature; Thermal resistance; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, 1997. INTELEC 97., 19th International
Conference_Location
Melbourne, Vic.
Print_ISBN
0-7803-3996-7
Type
conf
DOI
10.1109/INTLEC.1997.646045
Filename
646045
Link To Document