• DocumentCode
    3321564
  • Title

    Australian facility for the calibration of precision harmonics and flicker meters

  • Author

    Sky, Budov ; Hammond, G.M. ; Georgakopoulos, D.

  • Author_Institution
    Nat. Meas. Inst, Lindfield, NSW
  • fYear
    2008
  • fDate
    Sept. 28 2008-Oct. 1 2008
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The paper describes a precision measurement system developed at NMI, Australia for the calibration of three-phase instruments measuring harmonics of current up to 20 A, voltage fluctuation and flicker. Particular attention is given to establishing a traceable link to the Australian primary standards of electrical quantities. Current and voltage harmonics up to the 99th and fluctuating voltages can be generated and measured with relative uncertainties close to 1times10-5.
  • Keywords
    power conversion harmonics; power harmonic filters; flicker meters; power analysers; precision harmonics; precision measurement system; Australia; Calibration; Current measurement; Digital systems; Electromagnetic measurements; Measurement standards; Power measurement; Software measurement; Voltage fluctuations; Voltage measurement; flicker; harmonics; standards;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Harmonics and Quality of Power, 2008. ICHQP 2008. 13th International Conference on
  • Conference_Location
    Wollongong, NSW
  • Print_ISBN
    978-1-4244-1771-1
  • Electronic_ISBN
    978-1-4244-1770-4
  • Type

    conf

  • DOI
    10.1109/ICHQP.2008.4668831
  • Filename
    4668831