    Transformer Internal Over-Voltages Caused by Remote Energisation

  • Author

    Lapworth, J.A. ; Wilson, A.

  • Author_Institution
    Doble Power Test Ltd., Guildford
  • fYear
    2007
  • fDate
    16-20 July 2007
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    There have been several cases of dielectric faults and failures in power transformers identified internationally that have been associated with system operation. This paper discusses UK examples and concludes the evidence indicates internal over- voltages arising from part winding resonance. These resonances are initiated by remote energisation, either intentionally or by the action of automatic re-energisation schemes after line trips. Some designs are more prone to the problem, and it is here that diagnostics such as sweep frequency response analysis may give some indication as to designs more at risk.
  • Keywords
    fault diagnosis; overvoltage; power transformers; transformer windings; UK; automatic re-energisation scheme; dielectric fault diagnostics; over-voltages; power transformer failure; winding resonance; Circuit faults; Circuit testing; Dielectrics; IEC standards; Impulse testing; Lightning; Oil insulation; Power transformer insulation; Power transformers; Surges;