DocumentCode
3329825
Title
Loading Capability of Transformer in Over-excitation Condition
Author
Savaghebi, M. ; Gholami, A. ; Hooshyar, H.
Author_Institution
Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran
fYear
2007
fDate
16-20 July 2007
Firstpage
1
Lastpage
3
Abstract
Hot spot temperature is the main limiting factor of transformer loading. On the other hand, supposing the frequency being constant, voltage increase will result in transformer over-excitation. When the transformer is over-excited, the no load loss and subsequently the hot spot temperature will increase. Thus, the transformer loading will be restricted. In this paper, the problem of loading capability determination considering over-excited operation of the transformer is addressed. Necessary improvements are proposed in order to adapt the IEEE thermal model to this condition. Then, over-excitation effect on transformer loadability is illustrated using improved model. Simulation results show that ignoring the over-excitation effects may lead to transformer insulation lifetime reduction up to 20%.
Keywords
power transformers; IEEE thermal model; hot spot temperature; over-excitation condition; transformer loading capability; Cooling; Core loss; Differential equations; Frequency estimation; Heat transfer; Magnetic cores; Oil insulation; Petroleum; Power transformer insulation; Temperature;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society Conference and Exposition in Africa, 2007. PowerAfrica '07. IEEE
Conference_Location
Johannesburg
Print_ISBN
978-1-4244-1477-2
Electronic_ISBN
978-1-4244-1478-9
Type
conf
DOI
10.1109/PESAFR.2007.4498073
Filename
4498073