• DocumentCode
    3329825
  • Title

    Loading Capability of Transformer in Over-excitation Condition

  • Author

    Savaghebi, M. ; Gholami, A. ; Hooshyar, H.

  • Author_Institution
    Dept. of Electr. Eng., Iran Univ. of Sci. & Technol., Tehran
  • fYear
    2007
  • fDate
    16-20 July 2007
  • Firstpage
    1
  • Lastpage
    3
  • Abstract
    Hot spot temperature is the main limiting factor of transformer loading. On the other hand, supposing the frequency being constant, voltage increase will result in transformer over-excitation. When the transformer is over-excited, the no load loss and subsequently the hot spot temperature will increase. Thus, the transformer loading will be restricted. In this paper, the problem of loading capability determination considering over-excited operation of the transformer is addressed. Necessary improvements are proposed in order to adapt the IEEE thermal model to this condition. Then, over-excitation effect on transformer loadability is illustrated using improved model. Simulation results show that ignoring the over-excitation effects may lead to transformer insulation lifetime reduction up to 20%.
  • Keywords
    power transformers; IEEE thermal model; hot spot temperature; over-excitation condition; transformer loading capability; Cooling; Core loss; Differential equations; Frequency estimation; Heat transfer; Magnetic cores; Oil insulation; Petroleum; Power transformer insulation; Temperature;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Society Conference and Exposition in Africa, 2007. PowerAfrica '07. IEEE
  • Conference_Location
    Johannesburg
  • Print_ISBN
    978-1-4244-1477-2
  • Electronic_ISBN
    978-1-4244-1478-9
  • Type

    conf

  • DOI
    10.1109/PESAFR.2007.4498073
  • Filename
    4498073