Abstract :
Multipurpose shunt capacitor filters in a pulp and paper mill environment to reduce the starting voltage drop of a 23000 hp synchronous motor, provide load voltage control, and limit the harmonic current and voltage distortions in the distribution system are described. These three objectives are met by two single-tuned shunt filter banks of 10.75 and 4.6 MVAr installed on a single 13.8 kV bus. A digital computer-based study leading to the optimum design of the shunt filter banks is emphasized.<>
Keywords :
digital simulation; distribution networks; filters; harmonics; machine control; paper industry; power capacitors; power system analysis computing; starting; synchronous motors; voltage control; 10.75 MVA; 13.8 kV; 23000 hp; 4.6 MVA; design; digital simulation; distribution system; harmonic current; harmonic distortion control; harmonic voltage; load voltage control; paper mill; power capacitors; power systems; pulp mill; shunt capacitor filters; starting; synchronous motor; Active filters; Capacitors; Filter bank; Harmonic distortion; Power generation; Power harmonic filters; Power system harmonics; Reactive power; Synchronous motors; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 1991., Conference Record of 1991 Annual
Conference_Location :
Montreal, Quebec, Canada
Type :
conf
DOI :
10.1109/PAPCON.1991.239661
Filename :
239661
Link To Document :
بازگشت