Title :
Smarttrafo and flicker
Author :
Abdulrahman, H. ; Bauer, P.
Author_Institution :
Philips Power Solutions, Eindhoven
Abstract :
In this paper it is shown that the switching of the power electronic switches can be cause (source) of the flicker. A new switching technique implemented to control a single-phase tap changed-transformer in order to eliminate the internal flicker problem is investigated. The suggested method was subjected to both theoretical and experimental investigations. Further in this paper a method to mitigate a cyclic voltage flicker using electronically switched tap changed transformer is investigated. The idea of this method is based on injection of a signal, with the same frequency rate as that of the flicker, into the feedback path of the controller. This method utilizing electronically controlled tap-changed transformer provides flicker free secondary voltage
Keywords :
feedback; on load tap changers; power electronics; switches; cyclic voltage flicker; electronically switched tap changed transformer; feedback path; internal flicker problem elimination; power electronic switches; single-phase tap changed-transformer; smarttrafo; switching technique; Electrical equipment industry; Feedback; Frequency; IEC standards; Power electronics; Pulse width modulation; Switches; Testing; Voltage control; Voltage fluctuations; Smarttrafo; flicker;
Conference_Titel :
Future Power Systems, 2005 International Conference on
Conference_Location :
Amsterdam
Print_ISBN :
90-78205-02-4
DOI :
10.1109/FPS.2005.204214