    Changes in electrical insulation properties of fire resistant cables during a fire incident

  • Author

    Polansky, Radek ; Prosr, P. ; Pinkerova, Martina ; Vesely, Ondrej

  • Author_Institution
    Fac. of Electr. Eng., RICE Univ. of West Bohemia, Pilsen, Czech Republic
  • fYear
    2013
  • fDate
    June 30 2013-July 4 2013
  • Firstpage
    670
  • Lastpage
    673
  • Abstract
    This paper is focused on the comparison of the behavior of two low fire hazard cables of different construction under fire conditions. The fire barrier of the first one was created by glass and glass mica tape while the second one was protected by ceramifible silicone insulation. The insulation resistance between insulated cores of cables was measured and periodically recorded. The fire test was done according to IEC 60331, the whole test took 90 minutes of a burning and 15 minutes of cooling. The results show interesting changes in insulation properties of the cable in the first few minutes when the insulation resistance decreases by several orders of magnitude. On the other hand, during cooling the insulation, the state of cables is almost restored to its initial values.
  • Keywords
    cable insulation; cables (electric); cables insulated cores; ceramifible silicone insulation; electrical insulation properties; fire incident; hazard cables; insulation cooling; insulation resistance; time 15 min; time 90 min; Cable insulation; Electrical resistance measurement; Fires; Glass; Resistance; fire retardant; fire test; halogen free; insulation resistance; low fire hazard cable; plastics;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Solid Dielectrics (ICSD), 2013 IEEE International Conference on
  • Conference_Location
    Bologna
  • ISSN
    2159-1687
  • Print_ISBN
    978-1-4799-0807-3
  • Type

    conf

  • DOI
    10.1109/ICSD.2013.6619866
  • Filename
    6619866