DocumentCode
3343754
Title
Changes in electrical insulation properties of fire resistant cables during a fire incident
Author
Polansky, Radek ; Prosr, P. ; Pinkerova, Martina ; Vesely, Ondrej
Author_Institution
Fac. of Electr. Eng., RICE Univ. of West Bohemia, Pilsen, Czech Republic
fYear
2013
fDate
June 30 2013-July 4 2013
Firstpage
670
Lastpage
673
Abstract
This paper is focused on the comparison of the behavior of two low fire hazard cables of different construction under fire conditions. The fire barrier of the first one was created by glass and glass mica tape while the second one was protected by ceramifible silicone insulation. The insulation resistance between insulated cores of cables was measured and periodically recorded. The fire test was done according to IEC 60331, the whole test took 90 minutes of a burning and 15 minutes of cooling. The results show interesting changes in insulation properties of the cable in the first few minutes when the insulation resistance decreases by several orders of magnitude. On the other hand, during cooling the insulation, the state of cables is almost restored to its initial values.
Keywords
cable insulation; cables (electric); cables insulated cores; ceramifible silicone insulation; electrical insulation properties; fire incident; hazard cables; insulation cooling; insulation resistance; time 15 min; time 90 min; Cable insulation; Electrical resistance measurement; Fires; Glass; Resistance; fire retardant; fire test; halogen free; insulation resistance; low fire hazard cable; plastics;
fLanguage
English
Publisher
ieee
Conference_Titel
Solid Dielectrics (ICSD), 2013 IEEE International Conference on
Conference_Location
Bologna
ISSN
2159-1687
Print_ISBN
978-1-4799-0807-3
Type
conf
DOI
10.1109/ICSD.2013.6619866
Filename
6619866