DocumentCode :
3343754
Title :
Changes in electrical insulation properties of fire resistant cables during a fire incident
Author :
Polansky, Radek ; Prosr, P. ; Pinkerova, Martina ; Vesely, Ondrej
Author_Institution :
Fac. of Electr. Eng., RICE Univ. of West Bohemia, Pilsen, Czech Republic
fYear :
2013
fDate :
June 30 2013-July 4 2013
Firstpage :
670
Lastpage :
673
Abstract :
This paper is focused on the comparison of the behavior of two low fire hazard cables of different construction under fire conditions. The fire barrier of the first one was created by glass and glass mica tape while the second one was protected by ceramifible silicone insulation. The insulation resistance between insulated cores of cables was measured and periodically recorded. The fire test was done according to IEC 60331, the whole test took 90 minutes of a burning and 15 minutes of cooling. The results show interesting changes in insulation properties of the cable in the first few minutes when the insulation resistance decreases by several orders of magnitude. On the other hand, during cooling the insulation, the state of cables is almost restored to its initial values.
Keywords :
cable insulation; cables (electric); cables insulated cores; ceramifible silicone insulation; electrical insulation properties; fire incident; hazard cables; insulation cooling; insulation resistance; time 15 min; time 90 min; Cable insulation; Electrical resistance measurement; Fires; Glass; Resistance; fire retardant; fire test; halogen free; insulation resistance; low fire hazard cable; plastics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Solid Dielectrics (ICSD), 2013 IEEE International Conference on
Conference_Location :
Bologna
ISSN :
2159-1687
Print_ISBN :
978-1-4799-0807-3
Type :
conf
DOI :
10.1109/ICSD.2013.6619866
Filename :
6619866
Link To Document :
بازگشت