DocumentCode
3352467
Title
On the application of αβ-transformation for power systems frequency relaying
Author
Soliman, S.A. ; Alammari, R.A. ; El-Hawary, M.E.
Author_Institution
Dept. of Electr. Eng., Qatar Univ., Doha, Qatar
fYear
2001
fDate
2001
Firstpage
120
Lastpage
124
Abstract
This paper presents a new and very accurate algorithm for power system frequency measurement. The proposed algorithm is based on αβ-transformation of the three phase voltages or current waveforms in the relay location, where digital samples are available for the three phase waveforms. Having obtained the digital samples of one of the components, α-β components, the finite divided difference formulae are used to calculate the parameters of one of these components; the magnitude, the frequency and phase angle. The necessary formulae are derived within the text and effects of imbalance and harmonics contamination on the waveforms are discussed within the text
Keywords
frequency measurement; power system measurement; power system protection; power system relaying; relay protection; αβ-transformation; digital samples; finite divided difference formulae; frequency; frequency measurement; harmonics contamination; parameters calculation; phase angle; power systems frequency relaying; relay location; three phase current waveforms; three phase voltage waveforms; three phase waveforms; waveforms; Amplitude estimation; Digital relays; Frequency estimation; Frequency measurement; Pollution measurement; Power harmonic filters; Power system harmonics; Power system measurements; Power system relaying; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering, 2001. LESCOPE '01. 2001 Large Engineering Systems Conference on
Conference_Location
Halifax, NS
Print_ISBN
0-7803-7107-0
Type
conf
DOI
10.1109/LESCPE.2001.941637
Filename
941637
Link To Document