DocumentCode
3354298
Title
Statistical estimation method of remaining BDV and life expectancy for generator stator winding by using nondestructive insulation diagnostic data
Author
Nakayama, Akinobu
Author_Institution
Fuji Electr. Corp. Res. & Dev. Ltd., Kawasaki, Japan
Volume
2
fYear
1999
fDate
1999
Firstpage
528
Abstract
With the aim of properly estimating the remaining breakdown voltage (BDV) and life expectancy of generator stator winding insulation from nondestructive insulation diagnosis data, we have collected BDV and nondestructive data of the stator windings removed from 15 generators with rated voltage of 6.6 to 15.4 kV. Recently, we have calculated statistical correlation between BDV and nondestructive data for these coils, established statistical method of estimating remaining BDV by nondestructive insulation characteristics and multiple regression analysis, and are applying diagnosis for the operating generators
Keywords
electric breakdown; epoxy insulation; statistical analysis; stators; windings; 6.6 to 15.4 kV; BDV; generator stator winding; life expectancy; multiple regression analysis; nondestructive insulation diagnostic data; remaining breakdown voltage; statistical correlation; statistical estimation method; Character generation; Dielectrics and electrical insulation; Epoxy resins; Hydraulic turbines; Insulation testing; Life estimation; Nondestructive testing; Performance evaluation; Stator windings; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena, 1999 Annual Report Conference on
Conference_Location
Austin, TX
Print_ISBN
0-7803-5414-1
Type
conf
DOI
10.1109/CEIDP.1999.807858
Filename
807858
Link To Document