Leakage Current Pattern for Diagnosing the Contaminated Degree of Ceramic Insulators under Different Humidity
Author :
Jianbo Zhou ; Bo Gao ; Qingliang Wang ; Qiaogen Zhang
Author_Institution :
Sch. of Electr. Eng., Xi´an Jiaotong Univ., Xian
fYear :
2009
fDate :
27-31 March 2009
Firstpage :
1
Lastpage :
4
Abstract :
In this paper, leakage current flowing along contaminated ceramic insulators was separated into low frequency component and pulse component, which were detected respectively by Rogowski coil in artificial contamination tests. The effects of the operating voltage, the equivalent salt deposit density and humidity on the two characteristic components of leakage current were investigated. It is revealed that the peak of the pulse current component has a sudden rising during the increase of humidity, and the inflexion has been found to be closely related with the low frequency current. The diagnosing methods based on the combination of the two current components have been proposed eventually.
Keywords :
ceramic insulators; humidity; insulator contamination; insulator testing; leakage currents; Rogowski coil; artificial contamination test; contaminated ceramic insulator; humidity characteristics; leakage current pattern; pulse current component; salt deposit density; Ceramics; Coils; Contamination; Frequency; Humidity; Insulation; Insulator testing; Leak detection; Leakage current; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
Conference_Location :
Wuhan
Print_ISBN :
978-1-4244-2486-3
Electronic_ISBN :
978-1-4244-2487-0
Type :
conf
DOI :
10.1109/APPEEC.2009.4918459