Title :
Detection of Transformer Internal Faults by Using Independent Component Analysis
Author :
Kilic, Erdal ; Ozgonenel, Okan
Author_Institution :
Ondokuz Mayis Univ., Samsun
fYear :
2007
fDate :
11-13 June 2007
Firstpage :
1
Lastpage :
5
Abstract :
In this work it is aimed to detect transformer internal fault and magnetizing inrush currents by using independent component analysis (ICA). A laboratory transformer is used for real-time experiments to examine the suggested technique. Laboratory experiments cover turn to turn faults performed in primary and secondary windings and inrush conditions. Differential (Id) and restraint (Ir) currents are analyzed by ICA and MATLABtrade is used for required calculations. Transformer internal faults can be detected effectively with the proposed method.
Keywords :
fault location; independent component analysis; network analysis; transformer windings; MATLAB; differential current; fault detection; independent component analysis; laboratory experiment; laboratory transformer; restraint current; transformer internal fault; windings; Fault detection; Gaussian processes; Independent component analysis; Laboratories; MATLAB; Magnetic analysis; Surges;