DocumentCode
3358272
Title
Investigation and mitigation of harmonics from electric arc furnaces
Author
Ahmed, Emad E. ; Abdel-Aziz, M. ; El-Zahab, Essam Abou ; Xu, Wilsun
Author_Institution
Dept. of Electr. Eng., Alberta Univ., Edmonton, Alta., Canada
Volume
2
fYear
1999
fDate
9-12 May 1999
Firstpage
1126
Abstract
This paper investigates the harmonics produced from electric arc furnace (EAF) operation. It gives an example of arc furnace modeling as a harmonic voltage source. The total harmonic distortion of the voltage and the current at the point of common coupling (PCC) are addressed and the need to alleviate this distortion to cope with IEEE 519 recommended limits is discussed. The effect of arc length variation on the main electrical parameters of concern such as arc power, power factor and total harmonic distortion is investigated. Also, a sensitivity study to determine the effect of applying a capacitor bank alone on the voltage and current total harmonic distortion is presented.
Keywords
arc furnaces; capacitor storage; harmonic distortion; power factor; power harmonic filters; power system harmonics; IEEE 519 recommended limits; arc furnace modeling; arc power; capacitor bank; current distortion; electric arc furnaces; harmonic filters; harmonic voltage source; harmonics mitigation; point of common coupling; power factor; sensitivity study; total harmonic distortion; voltage distortion; Circuits; Electrodes; Feeds; Furnaces; Impedance; Power harmonic filters; Power system harmonics; Reactive power; Total harmonic distortion; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Computer Engineering, 1999 IEEE Canadian Conference on
Conference_Location
Edmonton, Alberta, Canada
ISSN
0840-7789
Print_ISBN
0-7803-5579-2
Type
conf
DOI
10.1109/CCECE.1999.808213
Filename
808213