DocumentCode
3358670
Title
Research on Lightning Over-Voltage Protection for 500kV GIS Substation
Author
Wang, Zhuo ; Li, Lei ; Gan, Ling Xia ; Li, Ning ; Li, Hong Tao
Author_Institution
Sch. of Electr. & Inf. Eng., BeiHua Univ., Jilin
fYear
2009
fDate
27-31 March 2009
Firstpage
1
Lastpage
5
Abstract
This paper combines incoming lines with 500 kV GIS substation, considering the influence of the impulse voltage-second characteristics of insulator strings, the impulse corona of incoming lines, the impulse grounding resistance of tower and the position of lightning. ATP-EMTP simulation program is applied to analyze the lightning over-voltage of 500 kV GIS substation. The result shows that impulse corona and the resistance of tower which is close to the substation have great influence on over-voltage, when lightning strike the tower which is close to terminal door-typed structure, the lightning over-voltage may be not the most serious, and when the over-voltage of the equipment is very serious, a group of arrester is installed which can decrease the over-voltage effectively. This research thinking takes safety and economy into account, which can provide new reference for the engineering.
Keywords
arresters; corona; earthing; gas insulated substations; lightning protection; overvoltage protection; substation protection; ATP-EMTP simulation program; GIS substation; arresters; impulse corona; impulse grounding resistance; impulse voltage-second characteristics; lightning over-voltage protection; lightning position; voltage 500 kV; Analytical models; Arresters; Corona; Geographic Information Systems; Grounding; Insulation; Lightning; Poles and towers; Substation protection; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
Conference_Location
Wuhan
Print_ISBN
978-1-4244-2486-3
Electronic_ISBN
978-1-4244-2487-0
Type
conf
DOI
10.1109/APPEEC.2009.4918694
Filename
4918694
Link To Document