Title :
Special Problems in Current Differential Protection Based on Bergeron Model
Author :
Bin Li ; Wenhua Chang ; Jiali He ; Zhi-Qian Bo
Author_Institution :
Key Lab. of Power Syst. Simulation & Control of Minist. of Educ., Tianjin Univ. Tianjin, Tianjin
Abstract :
UHV long transmission line takes on distinct characteristics of distributed parameters, and it has great capacitive currents. Traditional phase segregated current differential protection is severely influenced by distributed capacitive current. In order to realize differential protection with high sensitivity and reliability for UHV transmission line, phase segregated current differential protection based on Bergeron model had been put forward. The time-domain Bergeron model is widely used for calculation during fault transient period. In theory, new principle can completely compensate capacitive current, but in practical application, consecutive sample values are necessary to realize calculation of Bergeron equation. Therefore, it´s necessary to estimate the voltage or current values at non-sampling points. The paper proposes that the cubic spline interpolation algorithm can be used for calculation of Bergeron equation. Theoretical analysis and simulation tests show that the proposed method is valid and precise.
Keywords :
interpolation; power system protection; power system reliability; reliability; splines (mathematics); transmission lines; Bergeron model; UHV; cubic spline interpolation algorithm; distributed parameters; phase segregated current differential protection; reliability; sensitivity; transmission line; Analytical models; Equations; Interpolation; Power system transients; Protection; Spline; Testing; Time domain analysis; Transmission line theory; Voltage;
Conference_Titel :
Power and Energy Engineering Conference, 2009. APPEEC 2009. Asia-Pacific
Conference_Location :
Wuhan
Print_ISBN :
978-1-4244-2486-3
Electronic_ISBN :
978-1-4244-2487-0
DOI :
10.1109/APPEEC.2009.4918778