DocumentCode
3367627
Title
A proposal for energy saving in semiconductor fabs
Author
Suenaga, Osamu ; Kobayashi, Sadao ; Ohmi, Tadahiro
Author_Institution
Tokyo Electron Ltd., Japan
fYear
1999
fDate
1999
Firstpage
255
Lastpage
258
Abstract
This paper describes measurement of the energy consumption of diffusion furnaces and proceeds to propose several methods for energy saving. Measurements showed that cooling water consumes 71% of the energy, exhaust air 11% and dry coil (heat transferred to clean room air) 18%. In terms of cost (in Yen), cooling water accounts for 32%, exhaust air 46% and dry coil 22%. Proposals are raised for reducing the energy consumption of the furnace to less than a half of conventional ones by: employment of double layer cooler; replacement of exhaust from clean room air by partially treated air; and employment of heat insulation material for the furnace casing
Keywords
clean rooms; cooling; furnaces; integrated circuit manufacture; thermal insulation; clean room air; cooling water; cost; diffusion furnaces; double layer cooler; dry coil; energy consumption; energy saving; exhaust air; furnace casing; heat insulation material; partially treated air; semiconductor fabs; Coils; Cooling; Costs; Employment; Energy consumption; Energy measurement; Furnaces; Heat transfer; Proposals; Water heating;
fLanguage
English
Publisher
ieee
Conference_Titel
Semiconductor Manufacturing Conference Proceedings, 1999 IEEE International Symposium on
Conference_Location
Santa Clara, CA
ISSN
1523-553X
Print_ISBN
0-7803-5403-6
Type
conf
DOI
10.1109/ISSM.1999.808784
Filename
808784
Link To Document