• DocumentCode
    3369153
  • Title

    Safety issues related to the connection of MV and HV grounding systems outside substations

  • Author

    Rajotte, Y. ; Fortin, J. ; Lessard, G.

  • Author_Institution
    Hydro-Quebec, Que., Canada
  • Volume
    2
  • fYear
    2001
  • fDate
    2001
  • Abstract
    Hydro-Quebec conducted a research program aimed at specifying a method of feeding loads in HV (high voltage) lowers and more specifically, whether the HV and MV (medium voltage) grounding systems should be connected. Field measurements were made at three sites and the results were used to validate a MATLAB-based computer model. The main results of a sensitivity analysis identifying the key system parameters that influence touch voltages on LV (low voltage) and MV networks during faults on the HV system are presented. Finally, a method for feeding loads in HV towers is proposed
  • Keywords
    earthing; field strength measurement; poles and towers; power overhead lines; power system faults; power system protection; safety; substations; Canada; HV tower load feeding; Hydro-Quebec; MATLAB-based computer model; field measurements; power system faults; safety issues; sensitivity analysis; substation HV grounding systems; substation MV grounding systems; touch voltages;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Electricity Distribution, 2001. Part 1: Contributions. CIRED. 16th International Conference and Exhibition on (IEE Conf. Publ No. 482)
  • Conference_Location
    Amsterdam
  • ISSN
    0537-9989
  • Print_ISBN
    0-85296-735-7
  • Type

    conf

  • DOI
    10.1049/cp:20010743
  • Filename
    942879