DocumentCode :
3378432
Title :
An investigation into the impedance characteristics of a synchronous generator under loss of excitation condition
Author :
Moore, P.J. ; Stangenberg, A.
Author_Institution :
Sch. of Electron. & Electr. Eng., Bath Univ., UK
Volume :
2
fYear :
1998
fDate :
3-5 Mar 1998
Firstpage :
619
Abstract :
Under loss of excitation conditions, a synchronous generator can sustain internal damage and system stability can be lost. The loss of excitation condition can be detected using a mho-type distance relay. In this work, a micromachine based turboalternator simulator was subjected to the loss of excitation condition. Tests were conducted with the field winding both open and short-circuited, and for various loading conditions. An investigation of the mho-type relay behaviour was conducted based on digital recording of the machine terminal voltage and current signals. Results show that adequate relay performance is obtained
Keywords :
alternators; electric current measurement; electric impedance; electrical faults; exciters; machine testing; machine windings; turbogenerators; voltage measurement; digital recording; fault detection; field winding; impedance characteristics; internal damage; loading conditions; loss of excitation; mho-type distance relay; open-circuit; short-circuit; synchronous generator; terminal current signals; terminal voltage signals; turboalternator; Circuits; Frequency synchronization; Impedance; Induction generators; Power generation; Power system modeling; Power system relaying; Protective relaying; Rotors; Synchronous generators;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Energy Management and Power Delivery, 1998. Proceedings of EMPD '98. 1998 International Conference on
Print_ISBN :
0-7803-4495-2
Type :
conf
DOI :
10.1109/EMPD.1998.702758
Filename :
702758
Link To Document :
بازگشت