    Study on partial discharge characteristics of corona discharge in transformer oil under oscillating switching impulse voltage

  • Author

    Jianfeng Liang ; Liang Zhang ; Junhao Li ; Yanming Li

  • Author_Institution
    Sch. of Electr. Eng., Xi´an jiaotong Univ., Xi´an, China
  • fYear
    2013
  • fDate
    20-23 Oct. 2013
  • Firstpage
    1173
  • Lastpage
    1176
  • Abstract
    Partial discharge characteristics of corona discharge in transformer oil under the oscillating switching impulse voltage is investigated in this paper. A oscillating switching impulse voltage generator has been set up to produce the oscillating switching impulse voltages which satisfy the requirements of IEC60060-3 standard, furthermore the generator can produce positive or negative oscillating switching impulse voltage. A low inductance 50Ω resistor and 3.5MHz highpass filter is used to measure the partial discharge. Partial discharge of corona discharge in transformer oil under the positive and negative oscillating switching impulse voltage is carried out in this paper. Experiment results show that the amplitude of PD and the number of PD is increased by the amplitude of the oscillating switching impulse voltage, Moreover, corona discharge in transformer oil under oscillating switching impulse voltage exhibits the polar effect.
  • Keywords
    corona; high-pass filters; partial discharge measurement; transformer oil; corona discharge; frequency 3.5 MHz; high-pass filter; oscillating switching impulse voltage; partial discharge measurement; resistance 50 ohm; transformer oil; Corona; Discharges (electric); Oil insulation; Partial discharges; Power transformers; Switches; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
  • Conference_Location
    Shenzhen
  • Type

    conf

  • DOI
    10.1109/CEIDP.2013.6747436
  • Filename
    6747436