• DocumentCode
    3379362
  • Title

    About the power generation confirmation of the induction machine load and the influence on the islanding detection device

  • Author

    Igarashi, Hironobu ; Sato, Takanori ; Miyamoto, Kazunori ; Kurokawa, Kosuke

  • Author_Institution
    Japan Electrical Safety & Environment Technology Laboratories 5-14-12 Yoyogi Shibuya-ku, Tokyo, 151-8545 Japan
  • fYear
    2008
  • fDate
    11-16 May 2008
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    The photovoltaic generation system must have protection device and islanding detection devices to connect with utility line of the electric power company. It is regulated in the technological requirement Japanese guideline and the electric equipment technology standard that the country provides. The islanding detection device detected purpose install for blackout due to the accident occurrence of the earth fault and the short-circuit in the utility line. When the islanding detection device detects the power blackout, it is necessary to stop the photovoltaic generation system immediately. If the photovoltaic generation system is not immediately stopped that electricity comes to charge the utility power line very at risk. We had already known that the islanding detection device can´t detect the islanding phenomenon, if is there the induction machine load in the loads. Authors decided to investigate the influence that the inducement machine load gave to the islanding detection device. The result was confirmed the induction machine load had changed from the state of the electric motor into the state of the generator. And, the induction machine load that had entered the state of the generator changed into the electric motor driven at a synchronous speed and maintained the frequency. It was clarified not to be able to detect the islanding phenomenon because the frequency was maintained by the influence of the inducement machine load driven at a synchronous speed. The induction machine load was not able to be substituted by linear loads of an inductivity load and a capacitive load, etc. and was able to be confirmed from these results at the same time.
  • Keywords
    Electric motors; Electrical fault detection; Frequency; Guidelines; Induction generators; Induction machines; Photovoltaic systems; Power generation; Power system protection; Solar power generation;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Photovoltaic Specialists Conference, 2008. PVSC '08. 33rd IEEE
  • Conference_Location
    San Diego, CA, USA
  • ISSN
    0160-8371
  • Print_ISBN
    978-1-4244-1640-0
  • Electronic_ISBN
    0160-8371
  • Type

    conf

  • DOI
    10.1109/PVSC.2008.4922619
  • Filename
    4922619