DocumentCode :
3382775
Title :
Streamer propagation and breakdown under AC in mineral oil for gaps up to 80 cm
Author :
Lesaint, O. ; Gournay, P. ; Saker, A. ; Tobazéon, R. ; Aubin, J. ; Mailhot, M.
Author_Institution :
CNRS, Grenoble, France
fYear :
1996
fDate :
15-19 Jul 1996
Firstpage :
251
Lastpage :
254
Abstract :
This paper presents a study of prebreakdown and breakdown phenomena under ac voltage in mineral oil in very large gaps up to 80 cm. The investigations concern the measurement of breakdown voltages together with the recording of streamers. Experiments were conducted with rod-plane and sphere-plane electrode systems at different distances. The results describe breakdown mechanisms for moderately divergent fields and large gaps. A breakdown mode specific to the ac voltage is evidenced, in which “bursts” of streamers initiated at each halfwave can appear and lead to the lowest breakdown fields recorded under ac. Values of the average fields required for “burst” or “direct” breakdown modes are deduced from the experiments. The influence of particles is also considered
Keywords :
discharges (electric); electric breakdown; insulation testing; power transformer insulation; power transformer testing; power transformers; transformer oil; 30 to 80 cm; EHV transformer bushing shields; ac voltage; breakdown mechanisms; breakdown phenomena; breakdown voltages; burst breakdown mode; mineral oil; moderately divergent fields; particle influence; prebreakdown phenomena; rod-plane electrode systems; sphere-plane electrode systems; streamer propagation; very large gaps; Breakdown voltage; Electric breakdown; Electrodes; Geometry; Insulators; Minerals; Petroleum; Pollution measurement; Testing; Wire;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Conduction and Breakdown in Dielectric Liquids, 1996, ICDL '96., 12th International Conference on
Conference_Location :
Roma
Print_ISBN :
0-7803-3560-0
Type :
conf
DOI :
10.1109/ICDL.1996.565450
Filename :
565450
Link To Document :