DocumentCode :
3383607
Title :
The Differential Protection and Setting Calculation of the New-Type Converter Transformer
Author :
Jiang Fang-cai ; Xu Jia-zhu
Author_Institution :
Coll. of Electr. & Inf. Eng., Hunan Univ., Changsha, China
fYear :
2012
fDate :
27-29 March 2012
Firstpage :
1
Lastpage :
4
Abstract :
Aiming at the special winding connection of the new-type converting transformer, its connecting scheme of differential protection is proposed based on the establishment of the current transform equations. Adopting the ratio braking characteristic with three-broken line, and taking these effects into account including the unbalance current under the normal condition, current-transformer performance and existing output current when internal fault occurring, the setting values for the differential protection of the new-type converting transformer are calculated. At last, by the simulative calculation of various transformer operating states, the feasibility of the proposed scheme and the correctness of the setting calculation are verified.
Keywords :
current transformers; power transformer protection; transformer windings; transforms; converter transformer; current transformer performance; differential protection; internal fault occurring; ratio braking characteristic; setting calculation; special winding connection; three broken line; transform equations; transformer operating states; Circuit faults; Equations; Joining processes; Mathematical model; Phase transformers; Reliability; Windings;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location :
Shanghai
ISSN :
2157-4839
Print_ISBN :
978-1-4577-0545-8
Type :
conf
DOI :
10.1109/APPEEC.2012.6306897
Filename :
6306897
Link To Document :
بازگشت