Measuring molded case circuit breaker resistance
Author
Shea, John J. ; Bindas, John A.
Author_Institution
Westinghouse Sci. & Technol. Center, Pittsburgh, PA, USA
fYear
1992
fDate
18-21 Oct. 1992
Firstpage
159
Lastpage
165
Abstract
Molded case circuit breaker resistance is measured under various conditions to demonstrate the need for more standardized procedures when performing millivolt drop measurements. Breakers, rated at 600 V/sub ac//250 A/sub ac/ and 120/240 V/sub ac//50 A/sub ac/, with silver-tungsten (Ag-W) contacts are used to show that contact resistance can cause variability in circuit breaker resistance and to demonstrate the influence of current, time, contact temperature, and applied voltage on contact resistance. Based on these results, guidelines are developed for making reliable resistance measurements on molded-case circuit breakers (MCCB) when using the millivolt drop technique.<>
Keywords
circuit breakers; contact resistance; electric resistance measurement; electrical contacts; 120 V; 240 V; 250 A; 50 A; 600 V; Ag-W contacts; MCCB; contact resistance; contact temperature; current effect; millivolt drop measurements; molded case circuit breaker resistance; resistance measurements; time effect; Circuit breakers; Circuit testing; Computer aided software engineering; Contact resistance; Current measurement; Electrical resistance measurement; Guidelines; Performance evaluation; Temperature; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Contacts, 1992., Proceedings of the Thirty-Eighth IEEE Holm Conference on
Conference_Location
Philadelphia, PA, USA
Print_ISBN
0-7803-0576-0
Type
conf
DOI
10.1109/HOLM.1992.246920
Filename
246920
Link To Document