DocumentCode
3388266
Title
Wind Farm Tie-Line Protection Setting Based on Adaptive Current-Voltage Protection Principles
Author
Lei Xian-guo ; Duan Jian-dong
Author_Institution
Dept. of Electr. Eng., Xi´an Univ. of Technol., Xi´an, China
fYear
2012
fDate
27-29 March 2012
Firstpage
1
Lastpage
4
Abstract
Wind farm tie-lines need to complete the relay protection, but existing tie-lines, or not set protect at wind farm side, or the protection may be affected by wind farm characteristic and misoperation. This paper first analyzes the DFIG short circuit current characteristics; draw DFIG short circuit current be closely connected with fault time, fault modes, the Crowbar circuit whether action, voltage dips degree, etc. So setting the tie-line protection based on adaptive current-voltage protection principles. Finally, paper establishes the simulation model that base on Northern Shaanxi Lang´ergou wind farm to test the protection, the simulation software is DIgSILENT. Test results show that the protection configuration scheme is feasible; it can distinguish the internal fault or external fault and with excellent properties.
Keywords
power generation faults; power generation protection; relay protection; wind power plants; DFIG short circuit current characteristics; DIgSILENT; Northern Shaanxi Langergou wind farm; adaptive current-voltage protection principles; crowbar circuit; fault modes; fault time; relay protection; simulation software; wind farm tie-line protection setting; Circuit faults; Current measurement; Phase measurement; Rotors; Stators; Voltage measurement; Wind farms;
fLanguage
English
Publisher
ieee
Conference_Titel
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location
Shanghai
ISSN
2157-4839
Print_ISBN
978-1-4577-0545-8
Type
conf
DOI
10.1109/APPEEC.2012.6307124
Filename
6307124
Link To Document