DocumentCode
3388281
Title
Security testing of high impedance fault detectors
Author
Sultan, A.F. ; Swift, G.W.
Author_Institution
Dept. of Electr. & Comput. Eng., Manitoba Univ., Winnipeg, Man., Canada
fYear
1991
fDate
29-30 May 1991
Firstpage
191
Lastpage
197
Abstract
The security of high-impedance fault (HIF) relays is examined. Waveforms of HIFs as well as loads that behave to appear like HIFs were collected and processed. The detection parameters used in a number of present HIF detection algorithms were extracted and compared to test the algorithms´ ability to discriminate between faults and fault-like loads. It was found that there are loads that imitate HIFs, and that the present algorithms lack the security required under these load conditions. The high-impedance fault-like loads considered were: an arc welding machine; a personal computer; and a fluorescent light. It was found that arc welders can easily imitate HIF conditions, and that the tested algorithms showed insecurity when tested with an arc welder load
Keywords
fault location; load (electric); power system protection; relay protection; testing; arc welding machine; detection algorithms; detection parameters; fault location; fluorescent light; high impedance fault detectors; loads; personal computer; power system relay protection; security testing; Circuit faults; Circuit testing; Data acquisition; Electrical fault detection; Fault detection; Impedance; Instrument transformers; Power transformer insulation; Resistors; Soil;
fLanguage
English
Publisher
ieee
Conference_Titel
WESCANEX '91 'IEEE Western Canada Conference on Computer, Power and Communications Systems in a Rural Environment'
Conference_Location
Regina, Sask.
Print_ISBN
0-87942-594-6
Type
conf
DOI
10.1109/WESCAN.1991.160545
Filename
160545
Link To Document