Abstract
Localization XLPE cable defects with damped AC (DAC) voltage technique is suitable for medium-length cable (1000m~3000m), however, the precision decreases when the cable is shorter than 500m. For it is hard to distinguish the incident and reflected pulses in time using time domain reflectometry (TDR) with high oscillating frequency. To solve the problem, a compensation capacitor in parallel and optimization of detect unit and amplifier are proposed. This paper presents a laboratory experiment on 10kV XLPE short cables (<;500m) with four artificial typical defects. The results of defects detection and PD mapping are satisfactory, which prove the feasibility and effectiveness of damped AC voltage method to detect and locate the insulation defects of short cables.
Keywords
XLPE insulation; amplifiers; power cable insulation; power capacitors; time-domain reflectometry; DAC voltage; PD mapping; TDR; XLPE cable defects; amplifier; artificial typical defects; capacitor; damped AC voltage; defect detection; defect localization; high oscillating frequency; medium-length cable; short cables; time domain reflectometry; voltage 10 kV; Cable shielding; Needles; Partial discharges; Power cable insulation; Power cables;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2013 IEEE Conference on
Conference_Location
Shenzhen
Type
conf
DOI
10.1109/CEIDP.2013.6748178
Filename
6748178
Link To Document