  • Abstract
    As a kind of new protection device, fault current limiter has been used in power system .When the fault occured in the circuit, the transient model based on FCL will have some influences on transient stability of power system, distance protection and voltage sag. The paper will study the mechanism of influence on power system, a new distance protection setting method proposed after FCL being input and using the models and simulations of PSCAD-EMTDC to test and verify FCL´s influence on voltage sag. Analysis and simulation validation demonstrate that FCL not only improves transient stability of power system, but also reduce the influence of distance protection, as well as restrain the voltage sag effective.
  • Keywords
    equivalent circuits; fault current limiters; power supply quality; power system faults; power system transient stability; transient analysis; PSCAD-EMTDC; distance protection setting method; fault current limiter; power system; transient model; transient stability; voltage sag; Circuit faults; Circuit stability; Impedance; Power system stability; Transient analysis; Voltage fluctuations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6307239
  • Filename
    6307239