Title :
A Novel Gas Chromatography with a Pulsed Discharge Helium Ionization Detector for Measurements of Sulfur Hexafluoride Gas Sampled from Electrical Equipment
Author :
Xian-sheng Zhuang ; Li Wu
Author_Institution :
Electr. Power Sci. & Res. Inst. of Guangdong, Power Grid Corp., Guangzhou, China
Abstract :
Gas chromatography with a pulsed discharge helium ionization detector has the advantages of high sensitivity, wide linear range and universal use. It detects SF6, O2, N2, H2S, SO2, SOF2, SO2F2, S2OF10, CS2, CF4, C3F8, CO2, CO and other components with single injection. Comparison with other methods, it is probably more preferable for the analysis of the sulfur hexafluoride sampled from electrical equipment and will improve the technology of SF6 electrical equipment fault and latent fault diagnostics.
Keywords :
SF6 insulation; chromatography; fault diagnosis; insulator testing; SF6; SF6 electrical equipment fault; gas chromatography; latent fault diagnostics; pulsed discharge helium ionization detector; sulfur hexafluoride gas; Compounds; Detectors; Discharges (electric); Gas chromatography; Helium; Ionization; Sulfur hexafluoride;
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location :
Shanghai
Print_ISBN :
978-1-4577-0545-8
DOI :
10.1109/APPEEC.2012.6307330