• DocumentCode
    3392781
  • Title

    Analysis of Arrester Energy for 132vK Overhead Transmission Line Due to Back Flashover and Shielding Failure

  • Author

    Abu Bakar, Ab Halim ; Mokhlis, Hazlie ; Halim, Syahirah Abd ; Isa, Siti Sarah Mat ; Illias, Hazlee Azil

  • Author_Institution
    Dept. of Electr. Eng., Univ. of Malaya Power Energy Dedicated Adv. Center (UMPEDAC), Kuala Lumpur, Malaysia
  • fYear
    2012
  • fDate
    27-29 March 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    This paper presents analysis of lightning arrester energy due to back flashover and shielding failure for the purpose of installing transmission line arrester (TLA). This study simulated, analysed and validated with the installed lightning arresters on the 132kV transmission line in Malaysia by using PSCAD/EMTDC software. The arrester is based on IEEE frequency dependent model. The simulation result shows that the lightning arrester energy obtained through simulation is less than the rating installed at site.
  • Keywords
    arresters; failure analysis; lightning protection; power overhead lines; shielding; PSCAD/EMTDC software; TLA; arrester energy analysis; back flashover; lightning arrester analysis; lightning arrester energy; overhead transmission line; shielding failure; transmission line arrester; voltage 132 kV; Arresters; Conductors; Flashover; Lightning; Poles and towers; Power transmission lines; Wires;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
  • Conference_Location
    Shanghai
  • ISSN
    2157-4839
  • Print_ISBN
    978-1-4577-0545-8
  • Type

    conf

  • DOI
    10.1109/APPEEC.2012.6307344
  • Filename
    6307344