DocumentCode :
3393177
Title :
Harmonic Distortion Feature of AC Transformers Caused by DC Bias
Author :
Li, Zhen ; Yun, Yuxin
Author_Institution :
Inst. of Electr., EPRI of Shandong, Jinan, China
fYear :
2012
fDate :
27-29 March 2012
Firstpage :
1
Lastpage :
4
Abstract :
With regard to the first ± 660kV HVDC transmission line from Yinchuan to Qingdao, quantitative harmonic analysis of the main transformer in Yi Ming substation, about 65km away from the Qingdao converter station, is carried out based on an established nonlinear magnetic model by PSCAD/EMTDC. The results indicate that, both the odd and even harmonic components are getting much higher under DC bias than that without DC bias, which thereby makes the power transformers to severe harmonic sources. The relationship between the injected neural DC currents and the even harmonic ratio is established which presents further potential for developing inverse-current-injection based DC bias suppression scheme.
Keywords :
HVDC power transmission; harmonic distortion; power system harmonics; power transformers; power transmission lines; substations; AC transformers; DC bias suppression scheme; EMTDC; HVDC transmission line; PSCAD; Qingdao converter station; Yi Ming substation; Yinchuan; distance 65 km; harmonic analysis; harmonic distortion feature; inverse-current-injection; nonlinear magnetic model; power transformers; voltage 660 kV; Circuit faults; Harmonic analysis; PSCAD; Power system harmonics; Power transformers; Power transmission lines; Substations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Engineering Conference (APPEEC), 2012 Asia-Pacific
Conference_Location :
Shanghai
ISSN :
2157-4839
Print_ISBN :
978-1-4577-0545-8
Type :
conf
DOI :
10.1109/APPEEC.2012.6307366
Filename :
6307366
Link To Document :
بازگشت