Title :
Mitigation of current restrict of MV circuit breakers in shunt capacitor by metal oxide arrester
Author :
Zadeh, M. Karbalaye ; Abniki, H. ; Akmal, A. A Shayegani
Author_Institution :
Sch. of Electr. & Comput. Eng., Univ. of Tehran, Tehran, Iran
Abstract :
The Medium-voltage (MV) circuit breakers can fail to interrupt three-phase fault currents when power systems have transient recovery voltage (TRV) characteristics which exceed the rating of the circuit breaker. Surge arresters protect equipment of transmission and distribution systems. Arresters installed today are all metal-oxide (MO) arresters without gaps. This paper presents the application of MO surge arresters as a switching overvoltage protection of capacitor bank Medium-voltage circuit breakers. Based on an existing MV-Capacitor bank on PSCAD-EMTDC , the simulation is performed to show the effectiveness of the surge arrester in reducing circuit breaker TRVs and in minimizing the probability of circuit breaker restricts. The energy requirements of the surge arresters and the overvoltage protection levels of the capacitors for different surge arrester arrangements are calculated.
Keywords :
arresters; circuit breakers; overvoltage protection; power system faults; PSCAD-EMTDC; capacitor bank medium-voltage circuit breakers; distribution systems; metal oxide arrester; shunt capacitor; surge arresters protect equipment; switching overvoltage protection; three-phase fault currents; transient recovery voltage; transmission systems; Arresters; Capacitors; Circuit breakers; Fault currents; Medium voltage; Power system protection; Power system transients; Surge protection; Transient analysis; Voltage control; PSCAD-EMTDC; capacitor bank; metal-oxide arresters; transient recovery voltage (TRV);
Conference_Titel :
Power Electronics and Intelligent Transportation System (PEITS), 2009 2nd International Conference on
Conference_Location :
Shenzhen
Print_ISBN :
978-1-4244-4544-8
DOI :
10.1109/PEITS.2009.5407024