DocumentCode
3393729
Title
The testing of transformer oil using partial discharge techniques
Author
Zinoulis, T. ; Argirakis, I. ; Chadband, WG ; Auckland, DW
Author_Institution
Electr. Eng. Lab., Manchester Univ., UK
fYear
1996
fDate
15-19 Jul 1996
Firstpage
385
Lastpage
388
Abstract
The breakdown arc of a negative discharge is preceded by a burst of current pulses. Near to breakdown this burst of current pulses gives information about the size of the discharge and can be used to map its development. This paper develops the idea that, with the advent of fast digitizing oscilloscopes, the recording of such current pulse bursts can provide an alternative approach to the testing of insulating oils. The standard electrical breakdown test for transformer oil continues to be employed for the want of a better test, although it is acknowledged that the information it gives is of limited value. The proposed alternative approach, by avoiding actual breakdowns and testing over a longer period, can give more reliable (and reproducible) information not only about the breakdown voltage but also about the particle content of the oil
Keywords
arcs (electric); electric breakdown; impurities; insulation testing; partial discharges; power transformer insulation; power transformer testing; transformer oil; breakdown arc; breakdown voltage; burst of current pulses; discharge size; fast digitizing oscilloscopes; insulating oils; negative discharge; partial discharge techniques; particle impurities content; self-quenching process; shadowgraph system; transformer oil testing; Breakdown voltage; Electric breakdown; Electrodes; Laboratories; Oil insulation; Oscilloscopes; Partial discharges; Petroleum; Pulse transformers; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Conduction and Breakdown in Dielectric Liquids, 1996, ICDL '96., 12th International Conference on
Conference_Location
Roma
Print_ISBN
0-7803-3560-0
Type
conf
DOI
10.1109/ICDL.1996.565527
Filename
565527
Link To Document