DocumentCode :
3396566
Title :
Propagation behaviour of acoustic partial discharge signals in oil-filled transformers
Author :
Meunier, Robert ; Vaillancourt, Georges H.
Author_Institution :
Hydro-Quebec, Varennes, Que., Canada
fYear :
1996
fDate :
15-19 Jul 1996
Firstpage :
401
Lastpage :
404
Abstract :
In-service monitoring of power apparatus has become increasingly important for electric power utilities. In power transformers, many techniques are used for this purpose including gas-in-oil analysis and acoustic and electrical partial discharge detection. One of the most popular techniques is the detection of acoustic partial-discharge (PD) signals that propagate through the transformer oil. This technique is also widely used for the location of PD sources inside transformers. Unfortunately, the propagation of acoustic signals in large transformer tanks is not sufficiently known because it had previously only been studied in small tanks and the results extrapolated to large tank. This paper presents some of the results of a study done on a medium-size power transformer (25 MVA). Acoustic PD signals were generated by immersing either an electrical PD source or a piezoelectric crystal excited by a square-wave generator in the transformer oil. The ensuing tests included acoustic propagation in obstacle-free oil and oil with obstacles, over distances of up to 3 m. A very close fit to a simple analytical function was verified in obstacle-free oil. The reflection behaviour as a function of the angle of incidence of the wavefront on the tank wall was studied. A relationship was established between the apparent charge of electrical PD signals and the level of acoustic signals produced
Keywords :
acoustic signal processing; acoustic wave propagation; insulation testing; partial discharges; power system measurement; power transformer insulation; power transformer testing; transformer oil; 25 MVA; 3 m; acoustic partial discharge signals; angle of incidence; apparent charge; in-service monitoring; medium-size power transformer; obstacle-free oil; oil with obstacles; oil-filled transformers; propagation behaviour; reflection behaviour; square-wave generator; tank corner; transformer oil; Acoustic propagation; Acoustic reflection; Acoustic signal detection; Acoustic testing; Monitoring; Oil insulation; Partial discharges; Petroleum; Power transformers; Signal generators;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Conduction and Breakdown in Dielectric Liquids, 1996, ICDL '96., 12th International Conference on
Conference_Location :
Roma
Print_ISBN :
0-7803-3560-0
Type :
conf
DOI :
10.1109/ICDL.1996.565542
Filename :
565542
Link To Document :
بازگشت