DocumentCode :
3397220
Title :
New criterion to determine the nature of single-phase faults
Author :
Liu Haofang ; Chen Shuyong ; Liu Junling
Author_Institution :
Electr. Power Res. Inst., Beijing
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1
Lastpage :
5
Abstract :
The character of the voltage at the end of the opened phase conductor was studied and an improved voltage criterion was proposed to distinguish between temporary and permanent single-phase faults. The performance of the improved criterion is hardly influenced by load currents of healthy phases, transmission line length, fault distance or fault earth resistance. For EHV/UHV lines with shunt reactors, the improved method is also effective when a calculated capacitive coupling voltage is employed. Simulation tests show that the conclusions are correct.
Keywords :
conductors (electric); fault diagnosis; power transmission lines; EHV-UHV lines; capacitive coupling voltage; fault distance; fault earth resistance; load currents; opened phase conductor; permanent single-phase faults; transmission line length; Capacitance; Circuit faults; Conductors; Coupling circuits; Inductors; Mutual coupling; Power system stability; Power transmission lines; Shunt (electrical); Voltage; EHV/UHV transmission line; calculated capacitive coupling voltage; capacitive coupling voltage; resonant component; shunt reactor; single-phase fault; voltage criterion;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4244-1903-6
Electronic_ISBN :
978-1-4244-1904-3
Type :
conf
DOI :
10.1109/TDC.2008.4517116
Filename :
4517116
Link To Document :
بازگشت