DocumentCode :
3397345
Title :
Technique to decrease the electric field intensity on conductor surface using the asymmetrical-sized conductor bundle
Author :
Lee, Dong-il ; Shin, Koo-yong ; Lee, Seong-doo
Author_Institution :
Transm. Technol. Group, Korea Electr. Power Res. Inst., Daejeon
fYear :
2008
fDate :
21-24 April 2008
Firstpage :
1
Lastpage :
6
Abstract :
Corona discharges form at the surface of a transmission line conductor when the electric-field intensity on the conductor surface exceeds the breakdown strength of air. In order to decrease the electric-field intensity on the conductor surface, a new 6 conductor bundle has been studied. This bundle, asymmetrical-sized conductor bundle, consists of a large subconductor at the bottom two conductor positions in the 6-conductor bundle of each phase of the line. The electric field intensity on these two large subconductors is reduced which in turn reduces the corona noise. It is proven that the newly proposed method is a better solution for decreasing the electric- field intensity than either the conventional bundle or the asymmetric bundle proposed by EPRI(Electric Power Research Institute).
Keywords :
corona; multiconductor transmission lines; EPRI; Electric Power Research Institute; asymmetrical-sized conductor bundle; corona discharge; transmission line multisubconductor; Acoustic noise; Conductors; Corona; Electric breakdown; Fault location; Noise reduction; Power transmission lines; Surface discharges; Testing; Working environment noise; Asymmetric arrangement; Electric environmental impacts; Electric field intensity; Transmission line;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4244-1903-6
Electronic_ISBN :
978-1-4244-1904-3
Type :
conf
DOI :
10.1109/TDC.2008.4517124
Filename :
4517124
Link To Document :
بازگشت