Abstract :
High voltage direct current (HVDC) circuit breaker current switching test in a test laboratory is difficult due to the limited test power installation. Reproduction of test stresses by means of direct testing confronts huge investment. Synthetic testing, as an alternative method, could amplify the test power more than ten times with a relative low cost. A synthetic test circuit based on the most used parallel current injection method was developed for the current switching test of HVDC circuit breakers. This synthetic test circuit could reproduce the current and voltage stresses equal to or greater than those could meet in service.
Keywords :
HVDC power transmission; circuit breakers; switching; testing; HVDC transmission; current switching test; high voltage direct current circuit breaker; parallel current injection method; power installation; synthetic test circuit; Circuit breakers; Circuit testing; HVDC transmission; Laboratories; Stress; Switched capacitor circuits; Switches; Switching circuits; System testing; Voltage; HVDC circuit breakers; load current switching; synthetic test circuit; testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location :
Chicago, IL
Print_ISBN :
978-1-4244-1903-6
Electronic_ISBN :
978-1-4244-1904-3
Type :
conf
DOI :
10.1109/TDC.2008.4517172
Filename :
4517172
Link To Document :
بازگشت