• DocumentCode
    3398811
  • Title

    Combining synchronous UHF and IEC-compliant PD measurements for an effective noise suppression

  • Author

    Hoek, S.M. ; Weissenberg, W. ; Vogelsang, R. ; Plath, R. ; Ye, P. ; Rethmeier, K. ; Kraetge, A.

  • Author_Institution
    OMICRON Electron., Austria
  • fYear
    2009
  • fDate
    19-23 July 2009
  • Firstpage
    412
  • Lastpage
    416
  • Abstract
    On-side PD measurements are very often interfered by external disturbances as corona from neighboring systems and switching activity from the grid, respectively. Therefore no clear assignment of PD sources to the object is possible. However, a substantiated risk assessment requires such assignment and, even more, an identification and location of the PD fault. As the classical PD measurement methods, according to the IEC 60270, are very sensitive to external interferences, UHF detection methods are very common, allowing a high level of noise suppression. Due to the propagation characteristics of PD pulses in the UHF-range, a special UHF sensor, mounted close to the object to be tested, permits a sensitive focusing on partial discharges, as external noise and disturbances are highly attenuated. Hence, UHF signal detection ensures a high level of sensitivity and selectivity, respectively [1]. As a major disadvantage, UHF measurements can not be calibrated in terms of PD charge magnitudes. With international standards implying limit values to be specified in pico-Coulombs, the PD measurement needs a valid calibration to deliver comparable results. If possible two consecutive PD measurements can be done in order to A) detect PD in the UHF-range and B) evaluate them in the IEC-range. With a highly disturbed IEC-range, this may not be possible at all. With a modern synchronous PD measuring system it is possible to perform these two measurements simultaneously. Additionally, and as a main benefit, it is possible to use the UHF PD data as trigger source for the I EC PD measurement. This allows detecting PD with a high sensitivity and selectivity in the UHF-range, but allocating the appropriate PD level in terms of pico-Coulombs with the calibrated IEC-compliant PD detection.
  • Keywords
    IEC standards; UHF measurement; interference suppression; partial discharge measurement; risk management; IEC 60270; IEC-compliant PD measurements; UHF detection methods; noise suppression; on-side PD measurements; partial discharges; substantiated risk assessment; synchronous UHF; Corona; Fault diagnosis; IEC standards; Interference suppression; Noise level; Noise measurement; Partial discharges; Risk management; UHF measurements; UHF propagation; GIS; IEC 60270; UHF PD measurement; cable; on-side; synchronous PD measurement; transformer;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 2009. ICPADM 2009. IEEE 9th International Conference on the
  • Conference_Location
    Harbin
  • Print_ISBN
    978-1-4244-4367-3
  • Electronic_ISBN
    978-1-4244-4368-0
  • Type

    conf

  • DOI
    10.1109/ICPADM.2009.5252403
  • Filename
    5252403