Real time monitoring of the leakage current of 230 kV insulator strings under washing
Author
Oliveira, S. Campello ; Fontana, Eduardo ; Cavalcanti, F. J M M
Author_Institution
Grupo de Fotonica, Univ. Fed. de Pernambuco, Recife
fYear
2008
fDate
21-24 April 2008
Firstpage
1
Lastpage
4
Abstract
This paper reports the real time behavior of the leakage current flowing on insulator strings of a 230 kV substation tower during washing. Monitoring of two insulator strings in the tower is achieved by use of a pair of optical fiber sensors that detect samples of the leakage current waveforms and transmit those samples to a processing module via an optical link. It is observed that leakage current during washing may reach high peak levels, and the effectiveness of the washing can be inferred by the degree of leakage current after drying of the insulator strings. Direct monitoring of the leakage current can thus be used as an important guideline for proper washing procedures during this type of intervention as well as for determining the effectiveness of the procedure.
Keywords
computerised monitoring; fibre optic sensors; insulators; leakage currents; poles and towers; substation automation; insulator strings; leakage currents; optical fiber sensors; optical link; real time monitoring; substation tower; washing procedures; Dielectrics and electrical insulation; Flashover; Leakage current; Light emitting diodes; Monitoring; Optical fiber devices; Optical fiber sensors; Optical fibers; Poles and towers; Substations; Flashover; Insulators; Leakage current; Optical Fiber Transducers; Power Transmission Lines;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference and Exposition, 2008. T&D. IEEE/PES
Conference_Location
Chicago, IL
Print_ISBN
978-1-4244-1903-6
Electronic_ISBN
978-1-4244-1904-3
Type
conf
DOI
10.1109/TDC.2008.4517247
Filename
4517247
Link To Document